cpu315 2dp/pn 上電半個小時自動停機
鄭志武
發(fā)布于2012-12-14 11:59
1
0
標簽:
cpu3152dp/pn上電半個小時自動停機。
現(xiàn)象為ledsf亮,同時cpu處于stop狀態(tài),其它從站,2個et200m和em227模塊指示燈都正常。上電后再次重復(fù)。首先我把ob1里程序清空,還是會停機,說明我的程序沒問題。停機時候模塊指示燈都正常,所以請教高手指點,謝謝
診斷如下請大家?guī)兔Ψ治?br />diagnosticbufferofmodulecpu315-2pn/dp
orderno./descriptioncomponentversion
6es7315-2eh14-0ab0hardware4
---firmwarev3.2.7
bootloaderfirmwareexpansiona32.9.9
rack:0
slot:2
serialnumber:sc-c7uf67812012
event1of112:eventid16#38c4
distributedi/os:stationreturn
addressoftheaffecteddpslave:stationnumber:3
dpmastersystemid:1
log.baseaddressofthedpslave:inputaddress:2043
log.baseaddressofthedpmaster:2047
requestedob:rackfailureob(ob86)
obnotfound,ordisabled,orcannotbestartedinthecurrentoperatingmode
externalerror,outgoingevent
09:38:04.087am11/26/2012
(coding:16#38c4fe56c05407ff07fb0103)
event2of112:eventid16#456f
stopcausedbyrackfailure(obnotloadedornotpossible,ornofrb)
previousoperatingmode:run
requestedoperatingmode:stop(internal)
internalerror,incomingevent
09:38:03.169am11/26/2012
(coding:16#456fff840000010100000000)
event3of112:eventid16#39c4
distributedi/os:stationfailure
addressoftheaffecteddpslave:stationnumber:3
dpmastersystemid:1
log.baseaddressofthedpslave:inputaddress:2043
log.baseaddressofthedpmaster:2047
requestedob:rackfailureob(ob86)
priorityclass:26
externalerror,incomingevent
09:38:03.166am11/26/2012
(coding:16#39c41a56c05407ff07fb0103)
event4of112:eventid16#4302
modetransitionfromstartuptorun
startupinformation:
-timefortimestampatthelastbackeduppoweron
-singleprocessoroperation
current/laststartuptype:
-automaticwarmrestartafterbackeduppoweron
permissibilityofcertainstartuptypes:
-manualwarmrestartpermitted
-automaticwarmrestartpermitted
lastvalidoperationorsettingofautomaticstartuptypeatpoweron:
-automaticwarmrestartafterbackeduppoweron
previousoperatingmode:startup(warmrestart)
requestedoperatingmode:run
incomingevent
09:19:06.488am11/26/2012
(coding:16#4302ff68c700000008107710)
問題補充:
首先謝謝半瓶醋。
我加進去了ob86和ob122,出現(xiàn)的現(xiàn)象是不停機了,但是sf燈還是亮
3號從站配置如下
ps3075a
et200m153-1aa03-oxbo指示燈正常
do16*24322-1bh01-0aa0有輸出
ai8*13bit3311kf02-oabo
ai8*12bit331-7kf02-oabo2塊,bf燈正常
ao8*12bit332-5kf00_oabo2塊bf燈正常
檢查了dp接線正確,但是屏蔽線割掉了,沒有壓到貼片上。
設(shè)備正在調(diào)試,只進行了數(shù)字量調(diào)試,還沒有進行模擬量調(diào)試,我該怎么去檢查,怎么處理?
佳答案
requestedob:rackfailureob(ob86)
stopcausedbyrackfailure(obnotloadedornotpossible,ornofrb)
distributedi/os:stationfailure
從上述信息看,是機架故障:
、檢查模板的安裝,例如模板與機架之間的u型總線連接器、模板與前連接器的安裝是否緊固。
、檢查從站的通訊模塊或接口模塊的地址設(shè)定與組態(tài)的設(shè)定是否一致。