西門子PLC CPU 313C-2DP 頻繁報(bào)SF故障
劉玉蓉
發(fā)布于2014-11-14 17:18
2
0
標(biāo)簽:
PLC CPU 為6ES7313C-2DP 。2014年5月14-16日利用CPU的診斷功能,故障信息如下:
1)2014年5月13日I/O access error, reading;P area, double-word access, Access address: 352;Requested OB: I/O access error OB (OB122) ;External error, Incoming event。I/O access error, reading;P area, double-word access, Access address: 356;Requested OB: I/O access error OB (OB122) ;External error, Incoming event。
I/O access error, reading;P area, word access, Access address: 368;Requested OB: I/O access error OB (OB122) ;External error, Incoming event。I/O access error, reading;P area, word access, Access address: 372;Requested OB: I/O access error OB (OB122) ;External error, Incoming event。I/O access error, reading;P area, word access, Access address: 376;Requested OB: I/O access error OB (OB122) ;External error, Incoming event。
I/O access error, writing;P area, word access, Access address: 336;Requested OB: I/O access error OB (OB122);External error, Incoming event。I/O access error, writing;P area, word access, Access address: 338;Requested OB: I/O access error OB (OB122);External error, Incoming event。I/O access error, writing;P area, word access, Access address: 340;Requested OB: I/O access error OB (OB122);External error, Incoming event。I/O access error, writing;P area, word access, Access address: 342;Requested OB: I/O access error OB (OB122);External error, Incoming event。STOP caused by I/O management;Internal error, Incoming event。
2)2014年5月15日I/O access error, reading;P area, word access, Access address: 368;Requested OB: I/O access error OB (OB122);External error, Incoming event。I/O access error, reading;P area, word access, Access address: 372;Requested OB: I/O access error OB (OB122);External error, Incoming event。I/O access error, reading;P area, word access, Access address: 376;Requested OB: I/O access error OB (OB122);External error, Incoming event。
I/O access error, writing;P area, word access, Access address:336;Requested OB: I/O access error OB (OB122);External error, Incoming event。I/O access error, writing;P area, word access, Access address: 338;Requested OB: I/O access error OB (OB122);External error, Incoming event。I/O access error, writing;P area, word access, Access address: 340;Requested OB: I/O access error OB (OB122);External error, Incoming event。I/O access error, writing;P area, word access, Access address: 342;Requested OB: I/O access error OB (OB122);External error, Incoming event。
3)2014年5月16日I/O access error, reading;P area, double-word access, Access address:352;Requested OB: I/O access error OB (OB122);External error, Incoming event。檢查處理如下:
1)對PLC各模塊之間的總線連接器進(jìn)行檢查緊固。
2)更換SM338模塊和SM331模塊。
3)根據(jù)現(xiàn)場CPU模塊型號及版本情況,對PLC程序內(nèi)硬件配置情況進(jìn)行了修改完善,并重新下裝到PLC。
4)將PLC程序存儲卡格式化后重新寫入新程序。
目前模塊仍出現(xiàn)SF故障告警,請求指教
問題補(bǔ)充:
1、已經(jīng)更換過CPU模塊。2、338-342是模擬量輸出模塊地址,352-356是位置量SM338模塊地址,368-376是模擬量輸入地址。這些地址在程序內(nèi)都使用。3、I/O模塊連接器也更換過,并緊固過。
佳答案
你檢查一下你實(shí)際編程使用的地址,如PIW352等輸入地址是否與硬件組態(tài)范圍內(nèi)的地址編號。
回答補(bǔ)充問題:
既然這些使用的模擬量地址都在組態(tài)范圍,那只能是你模塊后“U”型連接器沒有插到位,或者前連接器的24V電源丟失引起了。