CPU314頻繁死機(jī).
劉玉蓉
發(fā)布于2014-11-10 17:24
1
0
標(biāo)簽:
CPU314沒(méi)有規(guī)律頻繁停機(jī)需要手動(dòng)才能運(yùn)行,MMC卡、CPU、電源、U型連接器都換了,還是不行,程序里也沒(méi)有空的輸入輸出點(diǎn)。接口模塊用的IM365,也換了。有個(gè)CP343-1,沒(méi)有換,不知道是不是這個(gè)原因。懷疑是有模塊故障。請(qǐng)指點(diǎn)。
Event 2 of 10: Event ID 16# 1381
Request for manual warm restart
STOP due to: STOP caused by I/O management
Startup information:
- Startup without modified system configuration
- No difference between setpoint and actual configuration
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Warm restart triggered by switch setting; last power on backed up
Permissibility of certain startup types:
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of automatic startup type at power on:
- Warm restart triggered by switch setting; last power on backed up
OB number: 100
Priority class: 27
Incoming event
03:28:32:307 pm 07/04/14
Event 3 of 10: Event ID 16# 4301
Mode transition from STOP to STARTUP
STOP due to: STOP caused by I/O management
Startup information:
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Warm restart triggered by switch setting; last power on backed up
Permissibility of certain startup types:
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of the automatic startup type at power on:
- Warm restart triggered by switch setting; last power on backed up
Previous operating mode: STOP (internal)
Requested operating mode: STARTUP (warm restart)
Incoming event
03:28:31:873 pm 07/04/14
Event 4 of 10: Event ID 16# 5961
Parameter assignment error in CPU module parameters
Parameter: module type
Input address: 2004 of the module with parameter assignment errors
Error type: type ID not detected ID
Operating mode: STOP (internal)
External error, Incoming event
03:28:04:228 pm 07/04/14
Event 5 of 10: Event ID 16# 5961
Parameter assignment error in CPU module parameters
Parameter: module type
Input address: 2000 of the module with parameter assignment errors
Error type: type ID not detected ID
Operating mode: STOP (internal)
External error, Incoming event
03:28:04:228 pm 07/04/14
Event 6 of 10: Event ID 16# 4358
All modules are ready for operation
Operating mode: STOP (internal)
Incoming event
03:28:04:131 pm 07/04/14
問(wèn)題補(bǔ)充:
CP型號(hào)和組態(tài)不一致,但是CP也沒(méi)有故障。是不規(guī)則的停機(jī)啊,如果組態(tài)不一致CPU就會(huì)報(bào)故障,為什么不規(guī)則停機(jī)。是不是和干擾有關(guān)系
佳答案
添加一些故障處理的空OB塊,軟啟動(dòng)塊OB100。檢查硬件是否分配了輸入地址2000-2007。檢查通訊是否正常。