當(dāng)前位置:技成首頁(yè) > 文章中心 > 技成百科 > PCS7組態(tài)300站與另外一個(gè)300站之間通訊問題,請(qǐng)大師分析下!

PCS7組態(tài)300站與另外一個(gè)300站之間通訊問題,請(qǐng)大師分析下!

劉玉蓉 發(fā)布于2014-10-11 17:13 132 0 標(biāo)簽:

PCS7組態(tài)300站與另外一個(gè)300站之間通訊出現(xiàn)問題,下面是我這邊CPU的診斷信息,OB82,OB86,OB122等都在,CPU沒有停機(jī),我這邊CPU診斷信息如下,請(qǐng)各位幫忙看看是什么問題,怎么解決,是他那邊的問題還是我這邊的。
Diagnostic buffer of module CPU 315-2 DP
Order No./ Description         Component                      Version                       
6ES7 315-2AH14-0AB0            Hardware                       2                             
- - -                          Firmware                       V 3.0.3                       
Boot Loader                    Firmware expansion             A 25.7.5                      
Rack:                          0
Slot:                          2

Serial number: S C-A8VU49842010

Event 1 of 10:  Event ID 16# 3842
Module OK
Module type: Distributed I/O slave
Input address:  2043
Requested OB: Diagnostic interrupt OB (OB82)
Priority class: 26
External error, Outgoing event
04:32:25.888 PM  11/03/1994

Event 2 of 10:  Event ID 16# 38C4
Distributed I/Os: station return
Address of the affected DP slave: station number:   32
DP master system ID:      1
Log. base address of the DP slave: Input address:  2044
Log. base address of the DP master:   2047
Requested OB: Rack failure OB (OB86)
Priority class: 26
External error, Outgoing event
04:32:21.727 PM  11/03/1994

Event 3 of 10:  Event ID 16# 3942
Module problem or maintenance necessary
Module type: Distributed I/O slave
Input address:  2043
Operating mode STOP
Module/submodule fault
Requested OB: Diagnostic interrupt OB (OB82)
Priority class: 26
External error, Incoming event
04:32:21.715 PM  11/03/1994

Event 4 of 10:  Event ID 16# 2942
I/O access error, reading
P area, word access, Access address:    422
Requested OB: I/O access error OB (OB122)
Priority class: 12
External error, Incoming event
04:32:21.672 PM  11/03/1994

Event 5 of 10:  Event ID 16# 2942
I/O access error, reading
P area, word access, Access address:    416
Requested OB: I/O access error OB (OB122)
Priority class: 12
External error, Incoming event
04:32:21.672 PM  11/03/1994

Event 6 of 10:  Event ID 16# 2942
I/O access error, reading
P area, word access, Access address:    418
Requested OB: I/O access error OB (OB122)
Priority class: 12
External error, Incoming event
04:32:21.671 PM  11/03/1994

Event 7 of 10:  Event ID 16# 2942
I/O access error, reading
P area, word access, Access address:    420
Requested OB: I/O access error OB (OB122)
Priority class: 12
External error, Incoming event
04:32:21.671 PM  11/03/1994

Event 8 of 10:  Event ID 16# 2942
I/O access error, reading
P area, word access, Access address:    434
Requested OB: I/O access error OB (OB122)
Priority class: 12
External error, Incoming event
04:32:21.671 PM  11/03/1994

Event 9 of 10:  Event ID 16# 2942
I/O access error, reading
P area, word access, Access address:    442
Requested OB: I/O access error OB (OB122)
Priority class: 12
External error, Incoming event
04:32:21.671 PM  11/03/1994

問題補(bǔ)充:
麻煩說仔細(xì)點(diǎn)可以嗎?我不是很懂,該怎么解決啊

佳答案

1、從Diagnostic buffer中提示:地址為32#的分布式DP I/O從站故障,引起OB82、OB122的中斷調(diào)用;訪問I/O地址416、418、420、422、434、442出錯(cuò)。
2、但我不明白的是:你在CPU315-2 DP中使用了PCS7軟件系統(tǒng)組態(tài),這是真的嗎?如果確信,那就是不兼容了!
3、PCS7軟件系統(tǒng)是適用在S7-400以上CPU的。即便是S7-400以上CPU,也不所有的CPU模塊硬件都匹配支持!

若有收獲,就點(diǎn)個(gè)贊吧!