當(dāng)前位置:技成首頁 > 文章中心 > 技成百科 > S7-PLCSIM模擬器SF燈總是突然亮,幫我看看.

S7-PLCSIM模擬器SF燈總是突然亮,幫我看看.

劉玉蓉 發(fā)布于2014-11-28 17:51 3 0 標(biāo)簽:

Event 1 of 80:  Event ID 16# 530D
New startup information in STOP mode
Startup prevented by:
- STOP request exists
- Cold restart or warm restart necessary
Startup information: 
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Automatic warm restart after backed up power on
Permissibility of certain startup types: 
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of automatic startup type at power on:
- Automatic warm restart after backed up power on
Operating mode: STOP (internal)
Incoming event
10:33:54.778 AM  03/13/2014
(Coding: 16# 530D  FF04  C777  0041  0810  7710)


Event 2 of 80:  Event ID 16# 4568
STOP caused by time error (OB not loaded, or not possible, or no FRB) 
Previous operating mode: RUN
Requested operating mode: STOP (internal)
Internal error, Incoming event
10:33:54.778 AM  03/13/2014
(Coding: 16# 4568  FF84  0000  0000  0000  0000)


Event 3 of 80:  Event ID 16# 3502
OB request error
No relevance for user (Z1): 0000
Cause: Cyclic interrupt clock pulse generator 8
Causing OB: Cyclic interrupt OB (OB  37) 
Causing priority class: 14
Requested OB: Timing error OB (OB80)
OB not found, or disabled, or cannot be started in the in the current operating mode
Internal error, Incoming event
10:33:54.775 AM  03/13/2014
(Coding: 16# 3502  FE50  C358  0000  1138  0E25)


Event 4 of 80:  Event ID 16# 3502
OB request error
No relevance for user (Z1): 0000
Cause: Cyclic interrupt clock pulse generator 8
Causing OB: Cyclic interrupt OB (OB  37) 
Causing priority class: 14
Requested OB: Timing error OB (OB80)
OB not found, or disabled, or cannot be started in the in the current operating mode
Internal error, Incoming event
10:33:54.771 AM  03/13/2014
(Coding: 16# 3502  FE50  C358  0000  1138  0E25)


Event 5 of 80:  Event ID 16# 3502
OB request error
No relevance for user (Z1): 0000
Cause: Cyclic interrupt clock pulse generator 8
Causing OB: Cyclic interrupt OB (OB  37) 
Causing priority class: 14
Requested OB: Timing error OB (OB80)
OB not found, or disabled, or cannot be started in the in the current operating mode
Internal error, Incoming event
10:33:54.735 AM  03/13/2014
(Coding: 16# 3502  FE50  C358  0000  1138  0E25)


Event 6 of 80:  Event ID 16# 4302
Mode transition from STARTUP to RUN
Startup information: 
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Automatic warm restart after backed up power on
Permissibility of certain startup types: 
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of automatic startup type at power on:
- Automatic warm restart after backed up power on
Previous operating mode: STARTUP (warm restart)
Requested operating mode: RUN
Incoming event
09:01:51.614 AM  03/13/2014
(Coding: 16# 4302  FF68  C700  0000  0810  7710)

佳答案

Causing OB: Cyclic interrupt OB (OB  37) 
循環(huán)中斷錯誤

Requested OB: Timing error OB (OB80)
需要下載OB80塊

原因:估計是你在OB37中的程序太多,運算時間超出了OB37的中斷時間。
解決辦法:
1、精簡OB37中的程序
2、將OB37中的程序放到OB35中
3、下載OB80塊,CPU會報錯,但不會停機

若有收獲,就點個贊吧!